Validation

Cable Sizing Calculator Verification

Hand-calculation cross-checks of the CCC cable sizing calculator against AS/NZS 3008.1.1 worked examples and the Nexans Olex 2017 Handbook (page 83 confirms its ratings are presented per AS/NZS 3008.1.1).

Methodology

Each verification case below is a self-contained engineering scenario. For each scenario we publish the inputs, the calculator output, the hand-calculation result and whether the two agree. We re-run these tests every time the calculator's lookup tables or calculation logic is updated. The Node.js spot-check script lives in the project repo at tools/cable-sizing/test/spotcheck.mjs.

Where the calculator output differs from the hand-calculation by more than ± 1 standard cable size, we investigate. Differences within 1 size typically reflect rounding in install-method derating factors or breakpoints in the standard cable size series (e.g. 25 mm² vs 35 mm²).

Scenario set v1.1 (Cu XLPE, Cu PVC, Cu EPR 110°C)

1. 100 A 3-phase sub-main, Cu XLPE multi-core, on tray spaced, 30 m

Inputs: Ib = 100 A, V = 400 V 3ph, Cu XLPE 4c, install = unenc_spaced, ambient = 40°C, grouping = 1, length = 30 m, VD limit = 5%
Hand-calc: derate 1.00, required Iz = 100 A. Smallest cable: 25 mm² (119 A). VD = 1.61 mV/A.m × 100 A × 30 m × 0.9 / 1000 = 4.35 V = 1.09% < 5%. Earth: 6 mm² per AS/NZS 3000 Table 5.1. PASS
Calculator: 25 mm² Cu XLPE multi-core, Iz 119 A, VD 1.09% — MATCH

2. 200 A 3-phase sub-main, Cu XLPE multi-core, on tray spaced, 50 m

Inputs: Ib = 200 A, V = 400 V 3ph, Cu XLPE 4c, install = unenc_spaced, ambient = 40°C, grouping = 1, length = 50 m, VD limit = 5%
Hand-calc: required Iz = 200 A. Smallest cable: 70 mm² (229 A). VD = 0.609 mV/A.m × 200 × 50 × 0.9 / 1000 = 5.48 V = 1.37%. Earth: 25 mm². PASS
Calculator: 70 mm² Cu XLPE multi-core, Iz 229 A, VD 1.37% — MATCH

3. 32 A 1-phase final sub-circuit, Cu PVC multi-core, enclosed conduit, 30 m, 35°C

Inputs: Ib = 32 A, V = 230 V 1ph, Cu PVC 2c, install = enc_in_air, ambient = 35°C, grouping = 1, length = 30 m, VD limit = 5%
Hand-calc: ambient derate ~1.05 for PVC at 35°C, required Iz = 32/1.05 = 30.5 A. Smallest cable: 4 mm² (PVC 2c ~38 A enclosed in air) gives derated 39.9 A. VD at 4 mm² PVC ~10 mV/A.m, Vd = 10 × 32 × 30 / 1000 = 9.6 V = 4.2%. PASS for VD but tight on capacity, may want 6 mm² for margin. Earth: 2.5 mm². PASS
Calculator: 6 mm² Cu PVC multi-core (calculator picks one size above for margin), VD 2.55% — CONSERVATIVE MATCH (1 size larger for safety)

4. 63 A 3-phase final, Cu XLPE multi-core, 4 grouped circuits, on tray touching

Inputs: Ib = 63 A, V = 400 V 3ph, Cu XLPE 4c, install = unenc_touching, ambient = 40°C, grouping = 4, length = 20 m, VD limit = 5%
Hand-calc: ambient = 1.00, grouping = 0.75, required Iz = 63 / 0.75 = 84 A. 16 mm² (83 A touching) gives derated 83 × 0.75 = 62 A < 63 A FAIL. Step up to 25 mm² (111 A × 0.75 = 83 A) >= 63 A PASS. VD at 25 mm² ~1.61 mV/A.m, Vd = 1.61 × 63 × 20 × 0.9 / 1000 = 1.83 V = 0.46%. Earth: 6 mm². PASS
Calculator: 25 mm² Cu XLPE multi-core, Iz 83 A, VD 0.46% — MATCH

5. 250 A 3-phase sub-main, Cu XLPE multi-core, 2 parallel cables, on tray spaced, 60 m

Inputs: Ib = 250 A, V = 400 V 3ph, Cu XLPE 4c, install = unenc_spaced, ambient = 40°C, grouping = 1, length = 60 m, VD limit = 5%, parallel = 2
Hand-calc: per cable current = 125 A, derate 1.00, required per-cable Iz = 125 A. Smallest: 35 mm² (147 A spaced). Total capacity 294 A. VD = 1.17 mV/A.m × 125 (per cable) × 60 × 0.9 / 1000 = 7.9 V = 1.97%. Earth: 10 mm² (per Cl 5.3.3.1.1 still based on single active CSA, not parallel total). PASS
Calculator: 2 × 35 mm² Cu XLPE multi-core, Iz total 294 A, VD 1.97% — MATCH

6. 100 A 3-phase IT load (non-linear, > 15% 3rd harmonic), 30 m

Inputs: Ib = 100 A, V = 400 V 3ph, Cu XLPE 4c, install = unenc_spaced, ambient = 40°C, grouping = 1, length = 30 m, VD limit = 5%, harmonic = nonlinear
Hand-calc: harmonic derate 0.84, required Iz = 100/0.84 = 119 A. 25 mm² (119 A) just meets. VD same as scenario 1 = 1.09%. Neutral sized full to active = 25 mm². PASS
Calculator: 25 mm² Cu XLPE multi-core (neutral 25 mm² full size), Iz 100 A (derated by 0.84), VD 1.09% — MATCH

Known limitations (transparent disclosure)

Data source audit trail

Need help with your next project?

CCC Engineering delivers commercial electrical, mechanical, hydraulic and fire protection design. Send an enquiry from the calculator and we'll come back within 1 business day.

Open calculator