Chilled Water Design: Pipe Sizing + Pump Head Guide
What You Need to Know
Chilled water systems cool large buildings. A chiller makes cold water at about 6°C. Pumps push that water through pipes to cooling coils in each room. The water absorbs heat, warms to about 12°C, and returns to the chiller. Getting the pipe sizes, pump heads, and temperatures right keeps the system efficient and the building comfortable.
The Rules
- Chilled water pipework pressure drop must not exceed 400 Pa/m for straight sections in constant-speed systems (NCC 2025, Table J6D8a)
- Variable-speed pump systems must keep pressure drop below 300 Pa/m for larger pipes (NCC 2025, Table J6D8b)
- Chilled water circuits must have automatic variable temperature control to improve chiller efficiency (NCC 2025, J6D3(1)(k))
- Circulating pumps must meet an energy efficiency index of 0.27 or less (NCC 2025, J6D8(2), per EU Regulation 622/2012)
- All chilled water pipe insulation must include a vapour barrier on the outside to prevent condensation (NCC 2025, Section J)
- Time switches are required for air-conditioning systems above 2 kW capacity (NCC 2025, J6D3(3))
What This Means in Practice
Take a 5,000 m² office building with a 500 kW cooling load. At a standard 6°C delta T (6°C supply, 12°C return), the flow rate works out to about 20 L/s. That needs a chiller, primary and secondary pumps, a pipe network, and cooling coils in each AHU (air handling unit) or FCU (fan coil unit).
Pipe sizing follows two rules. For pipes 50 mm and smaller, keep velocity below 1.2 m/s. For pipes larger than 50 mm, size by friction loss and stay under 400 Pa/m (ASHRAE Fundamentals, Chapter 33). The minimum velocity is 0.6 m/s. Below that, air bubbles will not travel to the vent points and the system fills with trapped air. Most designers target 1.5 to 3.0 m/s for mains.
Pump head covers every pressure drop in the longest pipe loop: pipe friction, fittings, the chiller evaporator (typically 40 to 80 kPa), AHU coils (30 to 60 kPa), and control valves (30 to 60 kPa). A typical commercial building needs 150 to 300 kPa of total pump head. Add a 10 to 20% safety margin, then match the flow and head to a pump curve from the manufacturer.
Key Design Decisions
Air-Cooled vs. Water-Cooled Chiller
Water-cooled chillers are more energy efficient but need a cooling tower on the roof. Air-cooled chillers sit on the roof or at ground level and need no tower. Pick water-cooled for buildings above 500 kW cooling load where roof space and water supply allow it.
Primary-Secondary vs. Variable Primary Flow
Primary-secondary pumping uses two loops: a constant-flow primary loop through the chillers and a variable-flow secondary loop through the building. Variable primary flow (VPF) uses one loop with variable-speed drives on all pumps. VPF saves about 15% pump energy but needs a bypass line and tighter BMS (building management system) control.
Standard Delta T vs. High Delta T
Standard Australian design uses a 6°C delta T (6°C supply, 12°C return). The international convention is 5.5°C (6.7°C supply, 12.2°C return). High delta T pushes to 8°C or more. Higher delta T means lower flow for the same cooling load, which means smaller pipes and smaller pumps.
Pipe Insulation and Vapour Barriers
All chilled water pipes must be insulated with a vapour barrier on the outside (NCC 2025, Section J). Without the vapour barrier, moisture in the air condenses on the cold pipe surface. This causes dripping, ceiling damage, and mould.
Who Needs to Know What
Need this engineered for your project?
Get a scoped fee proposal within 48 hours. Chartered engineers. Registered in NSW, VIC, and QLD.
References
- National Construction Code 2022, Volume One, Part J6 — Air-conditioning and ventilation
- National Construction Code 2022, Volume One, Part J5 — Air-conditioning and ventilation insulation
- AIRAH DA16, Air Conditioning Water Piping (design methods, pipe sizing, pressure loss data)
- AIRAH DA09, Air Conditioning Load Estimation and Psychrometrics (4th edition - cooling load calculation)
- ASHRAE Handbook - Fundamentals, Chapter 33: Pipe Sizing (international reference)
- ASHRAE Standard 90.1, Energy Standard for Buildings (international reference - delta T and pipe sizing requirements)