Design Memo
CCC-DM-2025-019

Fire Sprinkler System Design for Commercial Buildings

What You Need to Know

Fire sprinklers save lives and protect property. AS 2118.1 (the Australian Standard for automatic fire sprinkler systems) sets the design rules. The NCC (National Construction Code) tells you when a building needs sprinklers. Most commercial buildings over 3 storeys or 25 m in effective height must have them. Get the hazard class wrong, and the whole system is undersized.

The Rules

  • Commercial buildings over 25 m effective height need sprinklers; lower buildings may also need them depending on class and floor area (NCC 2025, Specification 20)
  • Sprinkler systems must comply with AS 2118.1-2017 as the deemed-to-satisfy solution (NCC 2025, Spec 20)
  • The hazard class sets the design: Light Hazard for offices, Ordinary Hazard for retail and car parks (AS 2118.1, Section 3)
  • Light Hazard design density is 2.25 mm/min over a 72 m² design area (AS 2118.1)
  • Ordinary Hazard OH2 design density is 5.0 mm/min over a 144 m² design area (AS 2118.1)
  • Water supply must last at least 30 minutes for Light Hazard and 60 minutes for Ordinary Hazard (AS 2118.1)
  • Maximum coverage per standard sprinkler head is 12 m² with a maximum spacing of 4.0 m (AS 2118.1)

What This Means in Practice

Take a 3-storey office building with 2,000 m² per floor. The offices are Light Hazard. At 2.25 mm/min over a 72 m² design area, the sprinkler demand is about 2.7 L/s (72 m² × 2.25 mm/min ÷ 60). That sounds small, but add in hose stream allowance and pipe friction losses, and the fire pump typically needs to deliver 10–15 L/s at 200–400 kPa.

The water supply tank for this system holds about 20,000 L for the sprinkler reserve alone. If the building also has hydrants (and most commercial buildings do), a combined tank of 40,000–50,000 L is common. That tank needs a pump room next to it, with space for a diesel and electric fire pump set. Allow at least 15–20 m² for the pump room and plan the tank location early.

If part of the building is retail at ground level (Class 6), that area steps up to Ordinary Hazard OH2. The design density more than doubles. The pipe sizes increase, the pump gets bigger, and the tank grows. Mixed-use buildings need the hydraulic design to account for the highest hazard class served by each zone.

Sprinkler heads in office ceilings sit on drops from the branch piping above. Each head covers up to 12 m² with 4.0 m maximum spacing. The heads typically need 25–300 mm clearance below the ceiling. The fire sprinkler contractor needs to coordinate with the HVAC ductwork, cable trays, and lighting in the ceiling void.


Key Design Decisions

1

Hazard Classification

Classify every area of the building before starting the design. Offices are Light Hazard. Retail is OH2. Car parks are OH1. Storage areas depend on what is stored and how high it is racked. One wrong classification changes pipe sizes, pump duty, and tank volume.

Trade-off: Higher hazard classifications cost more per square metre but match the actual fire risk. Underclassifying to save money will fail the certifier's review.
2

Wet Pipe vs. Pre-Action System

Use wet pipe for most commercial spaces. Wet pipe is cheaper, simpler, and more reliable. Use pre-action only where accidental water discharge would cause serious damage, such as server rooms, data centres, or archive stores.

Trade-off: Pre-action systems cost 2–3 times more than wet pipe per head and need detection panels, solenoid valves, and air compressors. Only specify where the risk justifies it.
3

Water Supply: Town Mains vs. On-Site Tank

Most Australian commercial buildings use on-site tanks with fire pumps. Town mains alone rarely provide enough pressure and flow. A combined sprinkler and hydrant tank reduces the number of tanks but needs careful sizing.

Trade-off: On-site tanks take up space (typically 20–50 m³) and need a pump room (15–20 m²). Town mains top-up keeps the tank smaller but depends on water authority approval.
4

Performance Solution vs. Deemed-to-Satisfy

A fire engineer can prepare a performance solution under NCC Clause A2.2 to modify sprinkler requirements. This may allow reduced coverage, alternative systems, or trade-offs with other fire safety measures.

Trade-off: Performance solutions need a fire engineer's report, peer review, and consent from the building certifier and fire brigade. Budget $15,000–40,000 in consultant fees and 4–8 weeks for the approval process.

Who Needs to Know What

Need this engineered for your project?

Get a scoped fee proposal within 48 hours. Chartered engineers. Registered in NSW, VIC, and QLD.

Get a Quote → 📞 0468 033 206

References

  1. AS 2118.1-2017, Automatic fire sprinkler systems — General systems
  2. National Construction Code 2022, Volume One, Specification 20 — Fire sprinklers
  3. National Construction Code 2022, Volume One, Part E1 — Fire-fighting equipment
  4. NFPA 13-2022, Standard for the Installation of Sprinkler Systems (international reference)
  5. Fire Protection Association Australia (FPAA), Technical Advisory Notes

Related design memos