Design Memo
CCC-DM-2026-122

HVAC Requirements for Medical Centres and Healthcare Facilities

What You Need to Know

Medical centres are classified as Class 9a under the National Construction Code. This classification triggers ventilation requirements well beyond what applies to standard commercial fitouts. The primary concern is infection control through airflow management, not just thermal comfort.

AS 1668.2:2024 significantly updated the healthcare ventilation requirements. The changes include higher air change rates for isolation rooms, new prescriptive HEPA filtration requirements, and more detailed room-by-room ventilation schedules. Any medical centre design started after the 2024 update must comply with the current edition.

The design challenge is managing multiple pressure relationships, filtration grades, and air change rates across a single facility. A consulting room, a procedure room, and an isolation room may all sit on the same floor but require completely different ventilation strategies.

Room-by-Room Requirements

1

General Consulting Rooms

Minimum 10 L/s per person outdoor air, consistent with standard office requirements under AS 1668.2. Temperature control to 22-24°C. Acoustic performance is critical in consulting rooms where patient confidentiality matters. Target noise criteria of NC 35-40.

These rooms do not need the elevated air change rates of treatment or procedure rooms, but they do need individual temperature control for patient comfort.

2

Treatment and Procedure Rooms

Procedure rooms require 6 to 12 air changes per hour depending on the procedure type and associated risk level. These rooms need higher outdoor air fractions than consulting rooms and may require HEPA filtration depending on the procedures performed. The 2024 update to AS 1668.2 introduced new prescriptive requirements for filtration in procedure rooms.

The air change rate directly affects equipment sizing and energy consumption. Over-specifying adds capital and running cost. Under-specifying creates compliance and infection control risk.

3

Infectious Isolation Rooms

The 2024 update increased the requirement to 12 air changes per hour, up from 6 in the previous edition. Isolation rooms must be maintained at negative pressure relative to the corridor to prevent airborne contaminants from migrating to adjacent spaces. HEPA filtration is required on the exhaust air path, referenced to AS 4260 for filter specification.

Negative pressure rooms need continuous monitoring and alarming to confirm the pressure relationship is maintained. This adds BMS complexity and ongoing maintenance cost.

4

Waiting Areas

Waiting areas in medical centres have high occupancy density relative to their floor area. Outdoor air rates must be calculated for peak occupancy, not average. These spaces also serve as the transition zone between the outside environment and clinical areas, so the ventilation design must account for dilution of any airborne contaminants brought in by patients.

5

Pharmacy Areas

Pharmacies require controlled temperature and humidity to maintain medication storage conditions. Typical requirements are 22-25°C and 30-60% RH. The HVAC system must maintain these conditions consistently, including during after-hours periods when the rest of the facility may be in setback mode.

6

Pathology Labs

Pathology and specimen handling areas require dedicated exhaust systems and must be maintained at negative pressure relative to surrounding spaces. Exhaust air from pathology labs cannot be recirculated. The exhaust discharge point must be located to prevent re-entrainment into the building's outdoor air intake.

Key Design Considerations

  • Infection control through ventilation is the primary design driver for healthcare facilities. Airflow direction, filtration grade, and air change rates all serve this purpose. AS 1668.2:2024
  • Pressure relationships between rooms must be mapped and maintained. Clean zones (consulting, recovery) operate at positive pressure. Contaminated zones (isolation, pathology) operate at negative pressure. The corridor typically serves as the neutral reference. AS 1668.2:2024
  • HEPA filtration is now a prescriptive requirement for isolation rooms and some procedure rooms under the 2024 update. Filters must comply with AS 4260 and be accessible for replacement and testing. AS 4260
  • Acoustic control is not optional in healthcare. Consulting rooms and recovery areas need quiet systems at NC 35-40. This often means larger ductwork, acoustic lining, and careful equipment selection.
  • Temperature control at 22-24°C for clinical areas requires multi-zone systems. Recovery rooms need individual temperature control for patient comfort.
  • Humidity in the range of 30-60% RH is typical for healthcare environments. Pharmacy and medication storage areas may have tighter requirements depending on the products stored.
  • Multi-zone separation between clean and dirty areas requires careful ductwork routing, dedicated air handling units or zoned systems, and potentially separate exhaust risers.

What This Means in Practice

A standard GP clinic with consulting rooms, a waiting area, and administration does not need hospital-grade systems. The outdoor air rates are comparable to a commercial office, and the main additions are acoustic treatment and zoning for patient comfort. Design fees for a small clinic (100-300 sqm) typically fall in the $4,000 to $10,000 range.

Once you add procedure rooms, pathology, or isolation facilities, the complexity increases significantly. Each of these room types introduces its own air change rate, pressure relationship, and filtration requirement. The mechanical system must maintain all of these simultaneously while the building is in normal operation. Design fees for a larger medical centre (300-1,000 sqm) with these features range from $10,000 to $30,000+.

The most common mistake is treating a medical centre fitout like a standard commercial project. The equipment, ductwork, and controls are more complex, and the compliance documentation is more extensive. Getting the ventilation strategy right at the design stage avoids costly modifications during construction or, worse, non-compliance at certification.


Who Needs to Know What

Need this engineered for your project?

Get a scoped fee proposal within 48 hours. Chartered engineers. Registered in NSW, VIC, and QLD.

Get a Quote → 📞 0468 033 206

References

  1. AS 1668.2:2024, The use of ventilation and airconditioning in buildings – Ventilation design for indoor air contaminant control
  2. National Construction Code 2022, Volume One – Building Code of Australia
  3. AS 4260, High efficiency particulate air filters (HEPA) – Classification, construction and performance
  4. AIRAH, HVAC&R Design Application Manual – Healthcare Facilities

Related design memos