Design Memo
CCC-DM-2025-052

NCC Building Classifications: Class 1-10 Services Guide

What You Need to Know

Every building in Australia gets a class number. That class sets the rules for fire, HVAC, plumbing, and power. NCC 2025 Part A6 defines ten classes, from houses (Class 1) to factories (Class 8). Get the class wrong and your services design starts with the wrong rules.

The Rules

  • The NCC defines building classes 1 through 10, each based on the building's use (NCC 2025, Part A6, Clauses A6G1–A6G12)
  • A building can have more than one class. Each part must meet the rules for its own class (NCC 2025, A6G12)
  • A minor use under 10% of a storey's floor area can adopt the main class. This does not apply to Class 2, 3, or 4 parts, labs, or early childhood centres (NCC 2025, A6G12)
  • Plant rooms take the same class as the main building they serve. The 10% minor-use rule does not apply to plant rooms (NCC 2025, A6G1)
  • Fire resistance levels, sprinkler triggers, and emergency systems all change based on class and building height (NCC 2025, Parts C, E1, and Specification 20)
  • Outdoor air ventilation rates depend on class and occupancy type. Class 5 offices need 10 L/s per person. Class 9a health-care spaces need 6–12 air changes per hour (AS 1668.2-2012, NCC 2025 Part F4)

What This Means in Practice

A 6-storey mixed-use building might have Class 6 retail on the ground floor, Class 5 offices on levels 1–4, and Class 2 apartments on level 5. Each part carries its own fire rating, ventilation rate, and services scope. The Class 6 retail needs Ordinary Hazard sprinkler design at 5.0 mm/min over 144 m². The Class 5 offices drop to Light Hazard at 2.25 mm/min over 72 m². The Class 2 apartments need smoke alarms in every unit and a different set of plumbing fixture counts.

The mechanical engineer sizes outdoor air systems by class. A Class 5 office at 10 L/s per person with one person per 10 m² needs 1 L/s per m² of outdoor air. A Class 6 restaurant at 10 L/s per person with one person per 2 m² needs 5 L/s per m². That five-fold jump in air volume changes duct sizes, plant capacity, and riser space. The class drives the maths.

Fire resistance levels (FRLs) also shift with class. A Type A construction Class 5 office at 4 storeys needs floor FRLs of 120/120/120 (minutes for structural adequacy/integrity/insulation). A Class 9a hospital at the same height can require higher FRLs depending on compartment type. Higher FRLs mean thicker slabs, more fire-rated penetrations, and bigger fire collars on every pipe and duct that passes through a floor or wall.


Key Design Decisions

1

Confirm the Class Before You Design

Lock in the building classification with the certifier at the start. Do not assume. A Class 3 hotel has different ventilation, fire, and accessibility rules than a Class 2 apartment block, even though both are residential.

Trade-off: Early classification meetings add 1–2 weeks to the program but prevent redesign later.
2

Design Each Part to Its Own Class

In mixed-use buildings, split the services design by class. The retail zone, office zone, and residential zone each carry their own ventilation rates, sprinkler hazard classes, and emergency system requirements.

Trade-off: Separate systems for each class cost more upfront but avoid compliance gaps at certification.
3

Watch the 10% Minor-Use Rule

A small cafe in an office building may not need a separate Class 6 services design if it occupies less than 10% of the storey. But the rule does not apply to residential parts, labs, or early childhood centres.

Trade-off: Using the 10% rule simplifies design but needs certifier agreement in writing before you rely on it.
4

Size Plant Rooms for the Highest Class Served

A plant room serving a Class 9a hospital floor needs more space than one serving a Class 5 office. Higher-class areas demand bigger air handling units, more redundant pumps, and standby power connections.

Trade-off: Oversizing plant rooms costs lettable area but avoids retrofit when tenant fit-out changes the class of a floor.

Who Needs to Know What

Need this engineered for your project?

Get a scoped fee proposal within 48 hours. Chartered engineers. Registered in NSW, VIC, and QLD.

Get a Quote → 📞 0468 033 206

References

  1. National Construction Code 2022 (NCC), Volume One, Part A6 — Building Classification (Clauses A6G1–A6G12)
  2. National Construction Code 2022 (NCC), Volume One, Part C — Fire Resistance
  3. National Construction Code 2022 (NCC), Volume One, Specification 20 — Fire Sprinklers
  4. National Construction Code 2022 (NCC), Volume One, Part E1 — Fire-fighting Equipment
  5. National Construction Code 2022 (NCC), Volume One, Part E4 — Visibility in an Emergency, Emergency Lighting
  6. National Construction Code 2022 (NCC), Volume One, Part F4 — Light and Ventilation
  7. National Construction Code 2022 (NCC), Volume One, Section J — Energy Efficiency
  8. AS 1668.2-2012, The Use of Ventilation and Airconditioning in Buildings — Mechanical Ventilation in Buildings
  9. AS 2118.1-2017, Automatic Fire Sprinkler Systems — General Systems
  10. AS/NZS 3500 series, Plumbing and Drainage

Related design memos