Design Memo
CCC-DM-2025-021

Smoke Detection and Alarm Systems

What You Need to Know

Smoke detectors save lives by finding fires early. AS 1670.1 (the Australian Standard for fire detection systems) sets the rules for design and installation. The NCC (National Construction Code) Part E1 tells you which buildings need them. Get the layout wrong, and your system will not pass commissioning.

The Rules

  • Each point-type smoke detector covers approximately 100 m² on a flat ceiling up to 4 m high, based on spacing tables (AS 1670.1)
  • Point-type smoke detectors are not effective above approximately 12 m ceiling height. Use beam detectors or aspirating systems instead (AS 1670.1)
  • Place a manual call point within 4 m of every exit door from a fire compartment (AS 1670.1)
  • The fire indicator panel (FIP, now formally called FDCIE) must sit at the main entrance, accessible to the fire brigade (AS 1670.1)
  • Each floor is a separate detection zone. No single zone should typically exceed 2,000 m² (AS 1670.1)
  • The building occupant warning system (BOWS) must reach at least 75 dB(A) for emergency tones in sleeping areas and be audible above background noise (minimum 65 dB, 10 dB above ambient) in all occupied areas (AS 1670.4)
  • Systems in specific building classes must connect to a fire brigade monitoring service per NCC Specification 20 — including Class 3 buildings with detection systems (certain occupancies), Class 9a (more than 20 patients), Class 9c, and systems activating smoke control (AS 1670.3)

What This Means in Practice

Take a typical 500 m² office floor with a 2.7 m ceiling. At roughly 100 m² per detector, you need at least 5 point-type smoke detectors on that floor. Room shape and obstructions usually push that number higher. Each detector sits on the ceiling, spaced so no point is more than approximately 5.8 m from a detector. The detectors wire back to a fire indicator panel (FIP) at the ground-floor main entry.

Add a manual call point beside every exit door. On a floor with 3 exit stairs, that means at least 3 manual call points. The FIP collects all signals and triggers the building occupant warning system (BOWS), which sounds an alert tone followed by an evacuation signal. The system also sends an automatic signal to the fire brigade through a monitoring service.

Higher ceilings change the rules. In a warehouse with an 8 m ceiling, smoke takes longer to reach a ceiling-mounted detector. The coverage area per detector drops, so you need more of them. Above approximately 12 m, point-type smoke detectors stop being effective. You switch to beam detectors (which sense smoke across a beam of light spanning the space) or aspirating smoke detection (ASD), which draws air through a pipe network to a central sensing unit. ASD is common in data centres, heritage buildings, and cold stores where early warning matters most.


Key Design Decisions

1

Point-Type Detectors vs. Aspirating Smoke Detection

Use point-type smoke detectors for standard office and retail spaces with ceilings up to 4 m. Switch to aspirating smoke detection (ASD) for high ceilings, high-value spaces, or areas where early warning is critical (data centres, archives, server rooms).

Trade-off: ASD typically costs 3-5 times more per zone than point-type detectors, but detects smoke minutes earlier. It also hides hardware in the ceiling void, which architects prefer.
2

Basic BOWS vs. EWIS

A building occupant warning system (BOWS) uses simple alert and evacuation tones. An emergency warning and intercom system (EWIS) adds two-way communication, zone-by-zone control, and voice announcements. NCC requires EWIS in buildings with an effective height above 25 m or where phased evacuation is needed (NCC 2025, Specification 20).

Trade-off: EWIS typically adds $15,000-40,000 or more over a basic BOWS, depending on building size. It requires speakers on every floor and a warden intercom point (WIP) at each warden station.
3

Detector Zones: How to Split Them

Keep each floor as its own zone. Within a floor, split zones at fire compartment walls. No single zone should cover more than 2,000 m². Smaller zones help the fire brigade find the fire faster.

Trade-off: More zones mean more cabling and a larger FIP. On a 10-storey building, expect 15-25 zones depending on floor plate size and compartmentation.
4

FIP Location and Fire Brigade Access

The FIP must be at the main entrance so firefighters can read it on arrival. If the building has two street frontages, the fire brigade will nominate the preferred entry. Confirm the FIP location with the local fire authority during design.

Trade-off: The FIP is a wall-mounted metal box, typically 600 mm wide or more depending on system size. Architects need to plan for it at the main lobby wall, visible on entry.

Who Needs to Know What

Need this engineered for your project?

Get a scoped fee proposal within 48 hours. Chartered engineers. Registered in NSW, VIC, and QLD.

Get a Quote → 📞 0468 033 206

References

  1. AS 1670.1:2024, Fire detection, warning, control and intercom systems — System design, installation and commissioning — Fire
  2. AS 1670.3:2018, Fire detection, warning, control and intercom systems — Fire alarm monitoring
  3. AS 1670.4:2024, Fire detection, warning, control and intercom systems — Sound systems and intercom systems for emergency purposes
  4. AS 7240 series, Fire detection and alarm systems (component-level requirements)
  5. National Construction Code 2022, Volume One, Part E1 and Specification 20
  6. AS 3786:2023, Smoke alarms using scattered light, transmitted light or ionisation
  7. AS 1851-2012, Routine service of fire protection systems and equipment

Related design memos