Design Memo
CCC-DM-2025-005

Toilet and Kitchen Exhaust Requirements

What You Need to Know

Toilet and kitchen exhaust air is dirty air. It contains odours, moisture, grease and contaminants that cannot go back into the building. AS 1668.2 bans recirculation of this air. It must go straight outside through a dedicated exhaust system. Kitchen exhaust also has strict discharge rules under AS 1668.2, including vertical discharge at roof level. Get either system wrong, and you risk failed compliance, odour complaints, and fire safety issues.

The Rules

  • Toilet exhaust must not be recirculated. It must discharge directly outside (AS 1668.2, Section 3)
  • Kitchen exhaust must not be recirculated. It must discharge directly outside (AS 1668.2, Section 3)
  • A single toilet, shower or bathroom needs at least 25 L/s of exhaust air (AS 1668.2, Table A1)
  • A domestic kitchen or laundry needs at least 40 L/s of exhaust air (AS 1668.2, Table A1)
  • Commercial kitchen exhaust rates are set by hood type and cooking process (AS 1668.2, Section 3)
  • Kitchen exhaust must discharge vertically at a minimum 5 m/s velocity from above the highest roof level (AS 1668.2, Cl 3.10.3)
  • Kitchen exhaust discharge points must be at least 6 m from property boundaries and sensitive receptors (AS 1668.2, Cl 3.10.3)
  • Kitchen exhaust systems exceeding 1,000 L/s must discharge vertically (AS 1668.2)
  • Make-up air must replace at least 80% of exhausted kitchen air (AS 1668.2)
  • Kitchen exhaust ductwork longer than 10 m with a flame source needs a UL1046-rated fire safety device (AS 1668.1)
  • Fire dampers must not be installed on cooking hood exhaust ducts (AS 1668.1)

What This Means in Practice

Take a ground-floor restaurant with a commercial kitchen in a multi-storey building. The kitchen exhaust duct must run from the hood, up through a dedicated riser, and discharge vertically at roof level. That riser needs space on every floor it passes through. The discharge point must sit at least 6 m from the property boundary and any outdoor air intakes.

If the kitchen exhaust is 1,200 L/s, you need a duct riser sized for that flow at 5 m/s discharge velocity. At 5 m/s, a round duct needs roughly 550 mm diameter. That riser must be fire-rated, have cleaning access every 3 m on horizontal runs, and have no fire dampers.

The kitchen also needs make-up air. If the exhaust is 1,200 L/s, the make-up air system typically supplies around 960 L/s (approximately 80% of exhaust). The rest comes as transfer air from the dining area, which keeps the kitchen at slight negative pressure. This stops cooking odours from pushing into other spaces. The make-up air unit and exhaust fan must be interlocked so they start and stop together.

For toilets, the maths is simpler. A bathroom block with 8 WC pans needs 8 × 25 L/s = 200 L/s of exhaust. This air goes straight outside through a dedicated duct. It cannot pass through the return air system or mix with supply air for other spaces.


Key Design Decisions

1

Kitchen Exhaust Discharge: Vertical vs. Treated

The default path is vertical discharge at roof level. But AS 1668.2:2024 now allows treated exhaust as an alternative. Treated systems use grease filtration and odour-removal technology to clean the air before horizontal discharge.

Trade-off: Vertical discharge costs less but needs a full-height riser. Treated exhaust avoids the riser but typically adds $30,000–80,000 in filtration equipment and ongoing filter replacement costs.
2

Kitchen Hood Type: Wall-Canopy vs. Island

Wall-mounted canopy hoods capture cooking effluent with less airflow than island hoods. An island hood needs higher exhaust rates because it is exposed on all sides.

Trade-off: Wall-canopy hoods need significantly less exhaust airflow than island hoods, which means smaller ducts, smaller fans, and lower energy costs. Plan the kitchen layout to put cooking equipment against walls where possible.
3

Make-Up Air Delivery Method

Make-up air can come from a dedicated make-up air unit (MAU) or from the building's general HVAC system. A dedicated MAU gives better control over temperature and airflow.

Trade-off: A dedicated MAU typically costs $15,000–40,000 but prevents the kitchen exhaust from pulling conditioned air out of the dining room. Without one, the building's cooling system works harder to replace the lost air.
4

Toilet Exhaust: Continuous vs. Intermittent

Toilet exhaust can run all the time or switch on with the lights and run for 10 minutes after. Continuous systems are simpler but use more energy.

Trade-off: Intermittent systems save energy in low-use areas. Continuous systems suit high-traffic toilets where the fan would rarely turn off anyway. For commercial buildings with occupied-hours scheduling, continuous operation during business hours is the most common approach.

Who Needs to Know What

Need this engineered for your project?

Get a scoped fee proposal within 48 hours. Chartered engineers. Registered in NSW, VIC, and QLD.

Get a Quote → 📞 0468 033 206

References

  1. AS 1668.2-2012, The use of ventilation and airconditioning in buildings — Part 2: Mechanical ventilation in buildings
  2. AS 1668.2:2024, The use of ventilation and airconditioning in buildings — Part 2: Mechanical ventilation in buildings (updated edition)
  3. AS/NZS 1668.1:2015, The use of ventilation and airconditioning in buildings — Part 1: Fire and smoke control in buildings
  4. National Construction Code 2022, Volume One, Part F6 — Light and ventilation
  5. National Construction Code 2022, Volume Two, Part 10.8 — Condensation management

Related design memos