Design Memo
CCC-DM-2026-037

Sub-Metering Requirements for Water

What You Need to Know

Water sub-meters track how much water different parts of a building use. Green Star and NABERS both require them. Without sub-meters, you cannot get a NABERS Water rating or earn Green Star water credits. The rules are straightforward: if a use is big enough to matter, it needs its own meter.

The Rules

  • Any common water use that takes 10% or more of total building water must have its own meter (Green Star Buildings v1, Credit 3)
  • Floors with multiple uses (e.g., office and retail) must have each use separately sub-metered (Green Star Buildings v1, Credit 3)
  • Floors with multiple tenants or owners must have each tenancy separately sub-metered (Green Star Buildings v1, Credit 3)
  • All meters must record readings at intervals of 1 hour or less and connect to a monitoring system (Green Star Buildings v1, Credit 3)
  • Meters must be commissioned and validated per the current NABERS non-utility meter protocol or NMI standards (Green Star Buildings v1, Credit 3)
  • Sub-meters must meet IEC standards and NABERS metering requirements (Green Star Buildings v1, Credit 3)
  • NABERS requires 12 months of quality-checked interval data before issuing a Water rating (NABERS Water, Chapter 6)
  • In Queensland, sub-meters are mandatory in new buildings with separate lots drawing from a shared water service (QLD Plumbing and Drainage Act)
  • Meter accuracy must meet Class 2 per NMI R 49.1 (AS 3565.1-2010)
  • From 1 May 2026, all new Green Star projects must register under Buildings v1.1 (GBCA)

What This Means in Practice

Take a 10-storey commercial office with a cooling tower, ground-floor retail, and a landscaped podium. You will need sub-meters on the cooling tower make-up line, the irrigation supply, each retail tenancy, the base building amenities on each floor, and the hot water plant. That is at least 15 meters before you count individual office tenancies.

Each meter needs a pulse output so the BMS can collect interval data. The BMS logs readings every 15 to 60 minutes. NABERS will not accept manual reads - you need 12 months of logged data before you can apply for a rating.

Meter placement matters. Install meters at ground level or in accessible risers. A meter buried behind a ceiling panel on level 8 will not get maintained. Leave at least 300 mm of clear space on each side for removal and calibration.

One real example: a Queensland retail centre installed monitoring on its cinema water supply and found overnight consumption 60 times higher than normal. Daily water costs dropped from $333 to $73 after the leak was fixed. That single meter paid for the entire sub-metering system within weeks.


Key Design Decisions

1

Pulse Output Meters vs. Manual-Read Meters

Use pulse output meters on every sub-meter location. Green Star requires data at 1-hour intervals or better, and NABERS needs 12 months of interval data. Manual-read meters do not satisfy either requirement.

Trade-off: Pulse output meters cost $50–150 more per meter than basic mechanical meters. For a 15-meter installation, that is $750–2,250 extra - but you cannot get your rating without them.
2

Where to Draw the Line on Sub-Metering

Meter every use that consumes 10% or more of total building water. Then add meters on cooling towers, irrigation, hot water plant, and each tenant demise. Skip small, fixed loads like a single basin in a fire control room.

Trade-off: Over-metering adds cost and maintenance burden. Under-metering means you cannot isolate leaks or prove compliance. Start with the Green Star minimum and add meters where leak detection has clear payback.
3

BMS Integration vs. Standalone Data Loggers

Connect all meters to the BMS for centralised monitoring. If the BMS scope does not include water metering, use standalone data loggers with cloud upload as a backup.

Trade-off: BMS integration costs $200–500 per meter point but gives the facility manager one dashboard. Standalone loggers cost $300–600 each and need their own platform, but they work when the BMS contract is already locked in.
4

Meter Location and Access

Place meters in ground-floor risers or accessible plant rooms. Avoid ceiling voids and locked service corridors. Every meter needs enough straight pipe upstream (5 pipe diameters minimum) for accurate readings.

Trade-off: Accessible locations may need longer pipe runs. Budget an extra 2–3 m of pipework per meter if the riser is not directly on the branch line.

Who Needs to Know What

Need this engineered for your project?

Get a scoped fee proposal within 48 hours. Chartered engineers. Registered in NSW, VIC, and QLD.

Get a Quote → 📞 0468 033 206

References

  1. Green Star Buildings v1 / v1.1, Credit 3 - Verification and Handover, Metering and Monitoring requirements
  2. NABERS Water rating rules, including Chapter 6 - Validating Non-Utility Meters for NABERS Ratings
  3. AS 3565.1-2010, Meters for Water Supply — Technical Requirements
  4. AS 3565.4-2007, Meters for Water Supply — In-Service Compliance Testing
  5. NCC 2025, Volume Three (Plumbing Code), Section B — Water Services
  6. QLD Plumbing and Drainage Act - Water sub-metering requirements for new premises
  7. WELS (Water Efficiency Labelling and Standards) scheme