Childcare Centre Ventilation and HVAC Requirements
What You Need to Know
Childcare centres are classified as Class 9b under the National Construction Code. They have some of the highest ventilation demands of any building type because of occupancy density: a single playroom may hold 20 or more children plus multiple staff members in a space under 100 square metres.
AS 1668.2:2024 requires a minimum outdoor airflow rate of 12 L/s per person for childcare centres. CO2 concentration must stay below 850 ppm above outdoor ambient. Natural ventilation alone rarely meets these targets in playrooms, so mechanical ventilation is standard practice.
Beyond air quality, childcare HVAC design must address acoustics (children and staff occupy these spaces all day), temperature control across rooms with different functions, and dedicated exhaust for nappy change areas and kitchens.
Room-by-Room Requirements
Playrooms
The primary occupied spaces. Minimum 12 L/s per person of outdoor air under AS 1668.2:2024. Calculate total occupancy carefully: a room licensed for 20 children with 4 staff members needs outdoor air for 24 people, or 288 L/s. Mechanical supply with filtered outdoor air is the most reliable solution. Temperature range of 20–24°C for comfort.
Sleep Rooms
Sleep rooms need the same outdoor air rates per person, but acoustic performance is the priority. Select equipment with low sound power levels and use duct attenuators to keep background noise well below normal playroom levels. Individual temperature control is preferred because sleep rooms are often occupied while adjacent playrooms are active, and metabolic loads differ between sleeping and active children.
Nappy Change Areas
Dedicated exhaust is required to maintain negative pressure relative to adjacent spaces. This prevents odours migrating into playrooms and corridors. Exhaust rates per AS 1668.2 for sanitary facilities apply. The exhaust must run continuously during occupied hours, not on a timer or occupancy sensor.
Kitchen and Food Preparation Areas
Commercial or semi-commercial kitchens within childcare centres need dedicated exhaust systems per AS 1668.2. Cooking hoods with grease filtration are required where gas or solid-fuel cooking occurs. Even centres with warm-up kitchens (no open-flame cooking) still need mechanical exhaust to control moisture and odours.
Outdoor Covered Areas
Covered outdoor play areas do not typically require mechanical ventilation if they are open on at least two sides. However, if the covered area is enclosed with screens, bi-fold doors, or roll-down blinds that restrict airflow, it may need to be assessed as an indoor space under the NCC. Air conditioning is sometimes provided for comfort in hot climates but is not a code requirement for genuinely outdoor spaces.
Key Design Considerations
- Outdoor air rates: Minimum 12 L/s per person for childcare occupancies. Count all children and staff in each room. (AS 1668.2:2024)
- CO2 concentration: Must not exceed 850 ppm above outdoor ambient. CO2 sensors in playrooms allow demand-controlled ventilation and provide a measurable compliance check. (AS 1668.2:2024)
- Acoustics: Children and staff spend 8–10 hours per day in these spaces. Select low-noise fan coil units or ducted systems, and install duct attenuators where supply ducts enter playrooms and sleep rooms. Background noise from HVAC should not interfere with speech or sleep.
- Temperature: Maintain 20–24°C in playrooms during occupied hours. Sleep rooms may need a slightly cooler set point. Individual zone control allows each room to be conditioned independently.
- Air intake location: Position outdoor air intakes away from loading docks, roads, car parks, waste storage areas, and exhaust outlets. AS 1668.2 specifies minimum separation distances. Poor intake placement introduces vehicle exhaust, odours, or recirculated stale air into the building.
- Fire safety: Class 9b buildings require smoke detection per NCC Section E. Smoke and fire dampers are needed where ductwork crosses fire compartment boundaries. Coordinate with the fire engineer on smoke hazard management requirements, particularly if the centre is within a mixed-use building.
What This Means in Practice
A typical 80-place childcare centre has 4–6 playrooms, 2–3 sleep rooms, a kitchen, multiple nappy change areas, staff rooms, and a reception area. Total outdoor air demand across all rooms can reach 1,500–2,500 L/s, depending on room sizes and occupancy. That volume of outdoor air needs to be filtered, heated or cooled, and distributed through ductwork to each room.
Split systems alone cannot handle the ventilation load. They recirculate indoor air and provide cooling or heating, but they do not introduce outdoor air. A ducted outdoor air system (sometimes called a fresh air handling unit) is needed alongside the comfort cooling system to meet AS 1668.2. Some designs combine both functions into a single packaged unit with an economy cycle.
Council DA conditions for childcare centres often include specific ventilation and noise requirements that go beyond the NCC. Review these conditions early in the design process. Common additions include acoustic reports demonstrating compliance with EPA noise limits at boundary, restrictions on rooftop plant visibility, and requirements for natural ventilation percentages in outdoor play areas.
If the childcare centre sits within a mixed-use development that includes residential apartments, BASIX requirements apply to the residential component and may influence plant room locations, intake and exhaust positions, and acoustic separation between the childcare and residential zones.
Who Needs to Know What
Need this engineered for your project?
Get a scoped fee proposal within 48 hours. Chartered engineers. Registered in NSW, VIC, and QLD.
References
- AS 1668.2:2024, The use of ventilation and airconditioning in buildings – Ventilation design for indoor air contaminant control
- National Construction Code 2022, Volume One, Part F6 (Natural ventilation) and Section E (Fire safety)
- AS 4254.1:2021, Ductwork for air-handling systems in buildings, Part 1: Flexible duct
- AS 1668.1:2015, The use of ventilation and airconditioning in buildings, Part 1: Fire and smoke control in buildings
- Education and Care Services National Regulations 2011 (National Quality Framework)
- Relevant council development consent conditions for childcare centre ventilation and acoustics