Economy Cycle Design for NCC Section J Compliance
What You Need to Know
An economy cycle uses cool outdoor air to reduce cooling load. NCC 2025 Part J6 requires one on any AHU (air handling unit) above a set airflow threshold. The threshold depends on your climate zone, and ranges from 2,000 L/s to 9,000 L/s.
The Rules
- An economy cycle is required when an AHU's total airflow meets or exceeds the threshold in Table J6D3 (NCC 2025, J6D3(1)(c))
- Climate zone 1 is exempt (NCC 2025, J6D3)
- Spaces needing humidity control are exempt (e.g., labs, cold stores) (NCC 2025, J6D3)
- Thresholds by climate zone: CZ2: 9,000 L/s, CZ3: 7,500 L/s, CZ4: 3,500 L/s, CZ5: 3,000 L/s, CZ6: 2,000 L/s, CZ7: 2,500 L/s, CZ8: 4,000 L/s (NCC 2025, Table J6D3)
- When the system shuts down, all motorised outdoor air and return air dampers must close (NCC 2025, J6D3(1)(l))
- The outdoor air system must still meet minimum ventilation rates per AS 1668.2 (NCC 2025, F6D6)
What This Means in Practice
Take an office building in Sydney (climate zone 5). Your AHU serves 1,500 m² of floor area at 6 air changes per hour. That gives a supply airflow of about 7,500 L/s. The Table J6D3 threshold for climate zone 5 is 3,000 L/s. Since 7,500 L/s exceeds 3,000 L/s, this AHU needs an economy cycle.
The economy cycle needs three motorised dampers: outside air, return air, and relief air. When outdoor air is cooler than return air (say 18°C outside vs. 24°C return), the BMS (building management system) opens the outside air damper and closes the return air damper. The relief damper opens to let excess air escape and prevent duct pressure buildup. The chiller stays off or runs at part load.
In a mild climate like Sydney or Melbourne, this can reduce chiller runtime by weeks or months each year. One Sydney CBD operator reported eliminating chiller use for 60 to 90 days annually. That cuts energy costs and extends chiller life.
Key Design Decisions
Temperature Control vs. Enthalpy Control
Temperature-based control compares outside and return air temperatures. It is simple and suits dry climates. Enthalpy-based control also measures humidity. It prevents bringing in hot, humid air that adds latent load.
Damper Sizing and Selection
Size outside air dampers to handle 100% of the AHU's supply airflow. Use opposed-blade dampers for better modulation. Match the relief air damper to the outside air damper size.
Minimum Outside Air During Economy Mode
The economy cycle must not drop below the minimum outdoor air rate set by AS 1668.2 (10 L/s per person for offices). The BMS needs a low-limit setpoint to prevent overcooling in winter.
Relief Air Path
Relief air must have a clear path out of the building. This usually means a relief fan or a barometric relief damper on the building exterior.
Who Needs to Know What
Need this engineered for your project?
Get a scoped fee proposal within 48 hours. Chartered engineers. Registered in NSW, VIC, and QLD.
References
- National Construction Code 2022, Volume One, Part J6 — Air-conditioning and ventilation (J6D3, Table J6D3)
- National Construction Code 2022, Volume One, Part F6 — Ventilation (F6D6)
- AS 1668.2-2012, The use of ventilation and airconditioning in buildings — Part 2: Mechanical ventilation in buildings
- AS 1668.2:2024, The use of ventilation and airconditioning in buildings — Part 2: Mechanical ventilation in buildings (current edition)
- AS 1668.1, The use of ventilation and airconditioning in buildings — Part 1: Fire and smoke control in buildings