Electrical Distribution Board Sizing and Layout
What You Need to Know
Every commercial building needs at least one distribution board. It splits the incoming power supply into separate circuits for lights, power outlets, HVAC, and other loads. Get the sizing wrong, and you run out of circuit breaker slots before the fit-out is done. Get the layout wrong, and the board fails its AS/NZS 3000 clearance requirements.
The Rules
- Distribution boards must comply with AS/NZS 61439 for construction and type testing (AS/NZS 3000, Cl 2.10.3.2)
- Calculate maximum demand using AS/NZS 3000 Appendix C — connected load multiplied by diversity factors gives the after-diversity maximum demand (AS/NZS 3000, Appendix C)
- Main switchboards need 1.0 m minimum clearance from all accessible faces in commercial buildings (AS/NZS 3000, Cl 2.10.2.2)
- All switchboards need 0.6 m unobstructed space with doors open or switchgear fully racked out (AS/NZS 3000, Figure 2.19)
- Access openings and doorways must be at least 0.9 m wide by 2.2 m high (AS/NZS 3000, Figure 2.20)
- Boards rated 800 A per phase or over 3 m long need two emergency exit paths - one exit is acceptable if there is 3 m clear space in front (AS/NZS 3000, Cl 2.10.2.2)
- Exit doors must open outward without keys or tools from inside
- The main switchboard must be easily accessible and near a building entrance - in multi-tenancy buildings, it must not sit within any single tenancy (AS/NZS 3000, Cl 2.10.2.2)
- Circuit breakers arranged so mechanisms open in the general “off” direction (AS/NZS 3000, Cl 2.10.3.4)
- Phase sequence must follow L1–L2–L3 - single-phase loads must be balanced evenly across all three phases
- Enclosures rated IP42 for indoor dry locations, IP66 for outdoor or wet areas - all live parts shielded (AS/NZS 3000, Cl 1.5.4)
What This Means in Practice
Take a small commercial building with 200 kVA of connected load. After applying diversity factors from AS/NZS 3000 Appendix C, the maximum demand might come down to around 140 kVA. At 400 V three-phase, that is about 200 A. You would size the main distribution board (MDB) at 250 A or 400 A to allow for future growth.
A typical MDB for a commercial building sits between 400 A and 1,600 A. Sub-distribution boards on each floor usually range from 100 A to 400 A. The board must handle not just the normal load but also the prospective fault current at that point in the network - the busbars and circuit breakers must withstand the thermal and mechanical stress of a short circuit.
Phase balancing matters. If you put all the lighting on one phase and all the power outlets on another, one phase runs hot while the others sit light. Spread single-phase loads across L1, L2, and L3. A common method alternates lighting circuits between phases.
For switchboard room lighting, you need 160 lux for general use, 400 lux for maintenance tasks, and at least 1 lux from emergency lighting.
Key Design Decisions
Board Rating - Match the Load or Allow Spare Capacity?
Size the board for the calculated maximum demand plus at least 20% spare capacity. A board with no spare ways forces an upgrade the moment a tenant adds a new circuit.
Fault Current Rating
Every board needs a fault current rating that matches or exceeds the prospective fault current at its location. The closer the board sits to the transformer, the higher the fault current. A typical MDB near a 1,000 kVA transformer might see 25 kA or more.
Single Main Board vs. Multiple Sub-Boards
For buildings over two storeys, use sub-distribution boards on each floor fed from the MDB. This reduces cable runs and voltage drop. Long cable runs from a single central board waste copper and increase voltage drop beyond the AS/NZS 3000 limit of 5%.
Spare Circuit Breaker Slots
Leave at least 2 spare three-phase circuit breaker slots and 4 spare single-phase DIN rail spaces in every board. Tenant fit-outs almost always add circuits that the base building design did not account for.
Who Needs to Know What
Need this engineered for your project?
Get a scoped fee proposal within 48 hours. Chartered engineers. Registered in NSW, VIC, and QLD.
References
- AS/NZS 3000:2018, Wiring Rules — Electrical installations
- AS/NZS 61439 series, Low-voltage switchgear and controlgear assemblies
- National Construction Code 2022, Volume One
- AS/NZS 3008.1, Electrical installations — Selection of cables