Design Memo
CCC-DM-2026-112

HVAC Design for Restaurants, Gyms, and Retail Fitouts

Every Fitout Is Different

A restaurant needs kitchen exhaust and high fresh air rates. A gym needs heavy cooling and ventilation for packed rooms. A retail shop needs comfort cooling and energy compliance. The HVAC system must match the use. Getting it wrong means failed inspections, uncomfortable spaces, or wasted money.

This memo covers what drives the mechanical design for each space type, what the Australian Standards require, and what you should plan for before your fitout starts.

Restaurants and Cafes

1

Kitchen Exhaust

Commercial kitchens must exhaust air at a minimum of 250 L/s per m² of cooking surface. This is set by AS 1668.1, Section 6. A 10 m² cook line needs at least 2,500 L/s of exhaust. The hood must capture all smoke, steam, and grease at the source.

Heavy cooking (chargrills, woks, deep fryers) often needs rates above the minimum. The hood type and filter setup depend on the cooking style.
2

Make-Up Air

All that exhausted air must be replaced. Make-up air is typically 65% to 85% of the exhaust rate. Without it, the kitchen runs under negative pressure. Doors slam. Smoke spills into the dining room. The exhaust fan works harder and burns out faster.

Make-up air can be tempered (heated or cooled) or untempered. Tempered air costs more to install but keeps the kitchen at a workable temperature.
3

Dining Area Cooling

The dining area needs its own cooling system, separate from the kitchen. Fresh air rates for diners are 10 L/s per person per AS 1668.2, Table A1. A 60-seat restaurant needs at least 600 L/s of outdoor air to the dining space alone.

Split systems work for small cafes. Larger restaurants with 80+ seats usually need a ducted or packaged system to handle the cooling load and fresh air volume.
4

Grease and Fire

Exhaust hoods over cooking equipment need grease filters. Heavy-duty cooking (open flame, chargrills) also needs a fire suppression system inside the hood. The duct from the hood to the fan must be grease-rated and fire-rated per AS 1668.1.

Grease filters need cleaning weekly. Neglected filters are the number one cause of kitchen fires and failed health inspections.
5

Budget

Engineering design: $8,000 to $20,000 depending on kitchen size and complexity. Installation: $40,000 to $150,000+ depending on exhaust run length, make-up air, and whether the building has existing ductwork.

Gyms and Fitness Centres

1

High Heat Gain from People

A person sitting in an office generates about 75 watts of heat. A person exercising generates 200 to 400 watts. A gym with 100 people working out adds 20 to 40 kW of heat from bodies alone. The cooling system must handle this on top of lighting, solar gain, and equipment loads.

Peak occupancy drives the design. A 24-hour gym with a 6 PM rush needs more cooling than the same space at 2 AM.
2

Fresh Air and Ventilation

AS 1668.2 requires outdoor air for gyms based on occupancy and activity level. For high-activity spaces, plan for 10 L/s per person. A 200-person gym floor needs at least 2,000 L/s of outdoor air. This is a large volume that must be conditioned before entering the space.

Under-ventilated gyms smell bad and feel stuffy. Members leave. Over-ventilated gyms waste energy. The design must match actual peak occupancy.
3

Air Movement

Moving air feels cooler. Ceiling fans or high-volume low-speed (HVLS) fans reduce the perceived temperature by 2 to 3 degrees. This lets you set the thermostat higher and save on cooling energy. HVLS fans are common in open-plan gyms with high ceilings.

Ceiling fans work in spaces with 3 m+ ceiling height. Low ceilings restrict fan options and force all the cooling work onto the air conditioning system.
4

Humidity

People sweating in a closed space raise the humidity fast. If relative humidity stays above 70%, the space feels clammy and surfaces grow mould. Dehumidification may be needed in coastal and subtropical locations. Pool areas and hot yoga studios always need it.

Standard split systems remove some moisture. Dedicated dehumidification adds cost but protects the building and keeps the space comfortable.
5

Budget

Engineering design: $5,000 to $15,000. Installation: $30,000 to $100,000 depending on floor area, ceiling height, and whether the space has existing mechanical services.


Retail Shops and Showrooms

1

Standard Comfort Cooling

Most retail spaces need straightforward comfort cooling. The design temperature is typically 22 to 24°C in summer. Occupancy is lower than a gym or restaurant, so the fresh air load is smaller. Standard occupancy rates from AS 1668.2 apply.

A small shop under 100 m² can often use wall-mounted split systems. Larger spaces or open-plan showrooms usually need ducted or VRF (Variable Refrigerant Flow) systems for even temperature distribution.
2

Section J Energy Compliance

Every new HVAC installation in a commercial building must comply with NCC 2025, Part J6. This sets minimum equipment efficiency, ductwork insulation, zoning, and controls. A Section J report or JV3 energy model is required for the construction certificate.

The Deemed-to-Satisfy (DtS) path is simpler and cheaper. The JV3 performance path gives more design freedom but needs an energy modeller. For a standard retail fitout, DtS is usually enough.
3

System Type

Split systems suit small tenancies. VRF systems suit multi-zone retail with different areas needing different temperatures (e.g., a showroom with a separate office and storeroom). Ducted packaged units suit large format retail like furniture stores or supermarkets.

Split systems cost less upfront but have limited zoning. VRF systems cost more but recover energy between zones and scale well for fitouts over 200 m².
4

Existing Building Services

Many retail fitouts happen inside existing shopping centres or strip retail. Check what the landlord provides. Some centres supply chilled water or condenser water. Others give you a bare shell with nothing. The base building system dictates your options.

Connecting to a landlord's central plant is often cheaper than installing standalone equipment, but you lose control over operating hours and temperature setpoints.
5

Budget

Engineering design: $3,000 to $8,000. Installation: $15,000 to $60,000 depending on tenancy size, system type, and base building provisions.

Who Needs to Know What

Need this engineered for your project?

Get a scoped fee proposal within 48 hours. Chartered engineers. Registered in NSW, VIC, and QLD.

Get a Quote → 📞 0468 033 206

References

  1. AS 1668.1:2015, The use of ventilation and airconditioning in buildings — Part 1: Fire and smoke control in buildings (Section 6: Kitchen exhaust systems)
  2. AS 1668.2:2012, The use of ventilation and airconditioning in buildings — Part 2: Mechanical ventilation in buildings (Table A1: Outdoor air requirements)
  3. National Construction Code 2022, Volume One, Part J6 — Air-conditioning and ventilation
  4. National Construction Code 2022, Volume One, Part F6 — Condensation management

Related design memos